Skip to content

Area of Rescue

With Talkaphone area of rescue (also called "area of refuge") products, you can be assured that you're relying on the best two-way communication devices during an emergency. Talkaphone is a trusted manufacturer for area of rescue systems. Browse our selection of area of rescue systems, phones and more.

Area of Rescue Analog Station, Flush Mounted

Area of Rescue Analog Station, Flush Mounted

MODEL NO: AOR-CSE-FM  •  AOR Analog Series

The AOR Analog Call station is an indoor, hands-free ADA-compliant communication endpoint for use with the AOR Series System in an area of rescue assistance.

  • Fully compliant with IBC, ADAAG, ICC A117.1 Ch. 7, and NFPA 72
  • Vandal resistant stainless steel faceplate and metal button
  • Phone line powered: no power supply or battery backup needed
  • Push button once to call, then speak hands-free
  • Two (2) LED indicators for hearing impaired (calling, answered)
  • Built-in auto-dialer can dial up to five (5) numbers. If first number does not answer or is busy, dials second number. If second number does not answer or is busy, dials third number—and so on.
  • Auto-answer on inbound calls allows security to monitor and initiate calls with the call station
  • Automatically inform attendant of the location of call station through recorded message that plays at the beginning of the call
  • Optional relay output
MORE ABOUT THIS PRODUCT

The AOR Analog Call station is an indoor, hands-free ADA-compliant communication endpoint for use with the AOR Series System in an area of rescue assistance.

FEATURES AND BENEFITS
  • Fully compliant with IBC, ADAAG, ICC A117.1 Ch. 7, and NFPA 72
  • Vandal resistant stainless steel faceplate and metal button
  • Phone line powered: no power supply or battery backup needed
  • Push button once to call, then speak hands-free
  • Two (2) LED indicators for hearing impaired (calling, answered)
  • Built-in auto-dialer can dial up to five (5) numbers. If first number does not answer or is busy, dials second number. If second number does not answer or is busy, dials third number—and so on.
  • Auto-answer on inbound calls allows security to monitor and initiate calls with the call station
  • Automatically inform attendant of the location of call station through recorded message that plays at the beginning of the call
  • Optional relay output
DOWNLOADS
Area of Rescue Analog Station, Surface Mounted

Area of Rescue Analog Station, Surface Mounted

MODEL NO: AOR-CSE-SM  •  AOR Analog Series

The AOR Analog Call station is an indoor, hands-free ADA-compliant communication endpoint for use with the AOR Series System in an area of rescue assistance.

  • Fully compliant with IBC, ADAAG, ICC A117.1 Ch. 7, and NFPA 72
  • Vandal resistant stainless steel faceplate and metal button
  • Phone line powered: no power supply or battery backup needed
  • Push button once to call, then speak hands-free
  • Two (2) LED indicators for hearing impaired (calling, answered)
  • Built-in auto-dialer can dial up to five (5) numbers. If first number does not answer or is busy, dials second number. If second number does not answer or is busy, dials third number—and so on.
  • Auto-answer on inbound calls allows security to monitor and initiate calls with the call station
  • Automatically inform attendant of the location of call station through recorded message that plays at the beginning of the call
  • Optional relay output
MORE ABOUT THIS PRODUCT

The AOR Analog Call station is an indoor, hands-free ADA-compliant communication endpoint for use with the AOR Series System in an area of rescue assistance.

FEATURES AND BENEFITS
  • Fully compliant with IBC, ADAAG, ICC A117.1 Ch. 7, and NFPA 72
  • Vandal resistant stainless steel faceplate and metal button
  • Phone line powered: no power supply or battery backup needed
  • Push button once to call, then speak hands-free
  • Two (2) LED indicators for hearing impaired (calling, answered)
  • Built-in auto-dialer can dial up to five (5) numbers. If first number does not answer or is busy, dials second number. If second number does not answer or is busy, dials third number—and so on.
  • Auto-answer on inbound calls allows security to monitor and initiate calls with the call station
  • Automatically inform attendant of the location of call station through recorded message that plays at the beginning of the call
  • Optional relay output
DOWNLOADS
Area of Rescue 8-Channel Command Unit

Area of Rescue 8-Channel Command Unit

MODEL NO: AOR-8  •  AOR Analog Series

Area of Refuge/Rescue (AOR) Command Unit (model AOR-8) is part of Talkaphone’s total AOR solution that accommodates up to 8 ADA-compliant Area of Refuge/Rescue stations.

  • Accommodates up to 8 Area of Rescue stations
  • AOR stations are powered by the command unit
  • Command unit can route an emergency phone call to a 911 center or other designated location

It consists of a command unit, a selected number of AOR stations (flush or surface mounted), and AOR signage to accommodate the selected number of AOR stations. The ADA-compliant AOR stations are powered by the command unit using one twisted-shielded pair cable from each AOR station to the command unit.

When the user initiates an emergency call from an AOR station, a tone is heard to confirm the call has been placed and an LED light indicates the call has been received. At the same time, the command unit’s strobe starts flashing and the siren is initiated. If there are other callers on the line, the command unit receives and queues the call. Each queued emergency call is displayed as a flashing red light on the command unit, which can be labeled for easy location identification. AOR stations can also be programmed to play a location identifier message when a call is answered. An active call is displayed as solid red. The command unit’s siren deactivates when the call is answered by local fire personnel. The strobe will deactivate only when all emergency lines have been cleared. Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.

The command unit can route an emergency phone call to a 911 center or other designated location via a TELCO line if no one is available to answer the call after an installer programmed amount of time. An uninterruptible power supply (UPS) is included to provide more than 4 hours of backup of the complete communications system.

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

https://talkaphone.com/area-of-rescue-resources-for-specifiers/

  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR  Series Command Unit.
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone
MORE ABOUT THIS PRODUCT

Area of Refuge/Rescue (AOR) Command Unit (model AOR-8) is part of Talkaphone’s total AOR solution that accommodates up to 8 ADA-compliant Area of Refuge/Rescue stations.

  • Accommodates up to 8 Area of Rescue stations
  • AOR stations are powered by the command unit
  • Command unit can route an emergency phone call to a 911 center or other designated location

It consists of a command unit, a selected number of AOR stations (flush or surface mounted), and AOR signage to accommodate the selected number of AOR stations. The ADA-compliant AOR stations are powered by the command unit using one twisted-shielded pair cable from each AOR station to the command unit.

When the user initiates an emergency call from an AOR station, a tone is heard to confirm the call has been placed and an LED light indicates the call has been received. At the same time, the command unit’s strobe starts flashing and the siren is initiated. If there are other callers on the line, the command unit receives and queues the call. Each queued emergency call is displayed as a flashing red light on the command unit, which can be labeled for easy location identification. AOR stations can also be programmed to play a location identifier message when a call is answered. An active call is displayed as solid red. The command unit’s siren deactivates when the call is answered by local fire personnel. The strobe will deactivate only when all emergency lines have been cleared. Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.

The command unit can route an emergency phone call to a 911 center or other designated location via a TELCO line if no one is available to answer the call after an installer programmed amount of time. An uninterruptible power supply (UPS) is included to provide more than 4 hours of backup of the complete communications system.

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

https://talkaphone.com/area-of-rescue-resources-for-specifiers/

FEATURES AND BENEFITS
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR  Series Command Unit.
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone
DOWNLOADS
Area of Rescue 24-Channel Command Unit

Area of Rescue 24-Channel Command Unit

MODEL NO: AOR-24  •  AOR Analog Series

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

  • Fully compliant with the IBC §1007, ADAAG §7, ICC A117.1, and NFPA 72 §24.5.3
  • Accommodates up to 24 ADA compliant Area of Rescue Stations
  • Stations are powered by Command Unit
  • LEDs on Command Unit indicate calling Station and line status
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone
MORE ABOUT THIS PRODUCT

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

FEATURES AND BENEFITS
  • Fully compliant with the IBC §1007, ADAAG §7, ICC A117.1, and NFPA 72 §24.5.3
  • Accommodates up to 24 ADA compliant Area of Rescue Stations
  • Stations are powered by Command Unit
  • LEDs on Command Unit indicate calling Station and line status
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone
DOWNLOADS
Area of Refuge 16 Channel Command Unit

Area of Refuge 16 Channel Command Unit

MODEL NO: AOR-16  •  AOR Analog Series

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations (AOR-16 requires 2 phone lines): line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also  recognize a AOR Series Command Unit.
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone

MORE ABOUT THIS PRODUCT

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

FEATURES AND BENEFITS
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations (AOR-16 requires 2 phone lines): line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate Stations that are waiting to be answered. When first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also  recognize a AOR Series Command Unit.
  • Siren is activated when Emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when Emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power back up in case of power failure
  • Includes built-in phone

DOWNLOADS
Area of Refuge 32 Channel Command Unit

Area of Refuge 32 Channel Command Unit

MODEL NO: AOR-32  •  AOR Analog Series

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

  • Fully compliant with the IBC §1007, ADAAG §7, ICC A117.1, and NFPA 72 §24.5.3
  • Accommodates up to 32 ADA compliant Area of Rescue stations
  • Stations are powered by command unit
  • LEDs on command unit indicate calling station and line status
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate stations that are waiting to be answered. When the first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Siren is activated when emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power backup in case of power failure
  • Includes built-in phone
MORE ABOUT THIS PRODUCT

The information on this page applies only to Revision 2.0 of the AOR-8 / AOR-16 / AOR-24 / AOR-32 models.  For Revision 1.0 documentation, please visit:

FEATURES AND BENEFITS
  • Fully compliant with the IBC §1007, ADAAG §7, ICC A117.1, and NFPA 72 §24.5.3
  • Accommodates up to 32 ADA compliant Area of Rescue stations
  • Stations are powered by command unit
  • LEDs on command unit indicate calling station and line status
  • Includes hardware to detect short/open conditions on cabling for each area of rescue station.  With this update, the system will also recognize a general ground fault condition.  Such trouble conditions will be annunciated and visually indicated at the AOR Series Command Unit.
  • On-site calling requires no outside phone lines
  • Off-site calling requires only one phone line for up to 8 Stations: line seizure eliminates need for dedicated phone line
  • Blinking LEDs indicate stations that are waiting to be answered. When the first call is completed, 2nd call is automatically placed, phone rings and strobe/siren is activated
  • Siren is activated when emergency call is first detected, shuts off when call has been answered
  • Strobe is activated when emergency call is first detected and remains active for duration of call
  • Built-in UPS provides 4-hour power backup in case of power failure
  • Includes built-in phone
DOWNLOADS
Fixed 5-Station Analog Area of Rescue Command Unit

Fixed 5-Station Analog Area of Rescue Command Unit

MODEL NO: AOR-5  •  AOR Analog Series
Talkaphone's new fully integrated fixed station analog command units accommodate up to five ADA-compliant area of rescue stations. The units provide both audible and visual indications for an incoming call - LED lights indicate the calling location. AOR command units are fully compliant with the NFPA 72 (2016) §24.10, IBC (2018) §1009, ICC A117.1 (2017) Ch. 7, and ADAAG (2010) Ch. 7.

• Automatically and continuously supervises for integrity (opens, shorts, and system ground fault), low battery backup, and 24VDC input power fail—alerts by relay output to an addressable fire panel, LED, and sounder

• On-site calling requires no outside phone line

• Off-site calling requires one (1) analog phone line (PSTN line)

• Solid LED indicates active call. Flashing LEDs indicate stations that are waiting to be answered. When first call is completed, second call is automatically placed and Command Unit rings. Multiple calls are placed in queue on a “first-in, first-out (FIFO)” basis.

MORE ABOUT THIS PRODUCT
Talkaphone's new fully integrated fixed station analog command units accommodate up to five ADA-compliant area of rescue stations. The units provide both audible and visual indications for an incoming call - LED lights indicate the calling location. AOR command units are fully compliant with the NFPA 72 (2016) §24.10, IBC (2018) §1009, ICC A117.1 (2017) Ch. 7, and ADAAG (2010) Ch. 7.
FEATURES AND BENEFITS

• Automatically and continuously supervises for integrity (opens, shorts, and system ground fault), low battery backup, and 24VDC input power fail—alerts by relay output to an addressable fire panel, LED, and sounder

• On-site calling requires no outside phone line

• Off-site calling requires one (1) analog phone line (PSTN line)

• Solid LED indicates active call. Flashing LEDs indicate stations that are waiting to be answered. When first call is completed, second call is automatically placed and Command Unit rings. Multiple calls are placed in queue on a “first-in, first-out (FIFO)” basis.

DOWNLOADS
Fixed 10-Station Analog Area of Rescue Command Unit

Fixed 10-Station Analog Area of Rescue Command Unit

MODEL NO: AOR-10  •  AOR Analog Series
Talkaphone's new fully integrated fixed station analog command units accommodate up to 10 ADA-compliant area of rescue stations. The units provide both audible and visual indications for an incoming call - LED lights indicate the calling location. AOR command units are fully compliant with the NFPA 72 (2016) §24.10, IBC (2018) §1009, ICC A117.1 (2017) Ch. 7, and ADAAG (2010) Ch. 7.

• Automatically and continuously supervises for integrity (opens, shorts, and system ground fault), low battery backup, and 24VDC input power fail—alerts by relay output to an addressable fire panel, LED, and sounder

• On-site calling requires no outside phone line

• Off-site calling requires one (1) analog phone line (PSTN line)

• Solid LED indicates active call. Flashing LEDs indicate stations that are waiting to be answered. When first call is completed, second call is automatically placed and Command Unit rings. Multiple calls are placed in queue on a “first-in, first-out (FIFO)” basis.

MORE ABOUT THIS PRODUCT
Talkaphone's new fully integrated fixed station analog command units accommodate up to 10 ADA-compliant area of rescue stations. The units provide both audible and visual indications for an incoming call - LED lights indicate the calling location. AOR command units are fully compliant with the NFPA 72 (2016) §24.10, IBC (2018) §1009, ICC A117.1 (2017) Ch. 7, and ADAAG (2010) Ch. 7.
FEATURES AND BENEFITS

• Automatically and continuously supervises for integrity (opens, shorts, and system ground fault), low battery backup, and 24VDC input power fail—alerts by relay output to an addressable fire panel, LED, and sounder

• On-site calling requires no outside phone line

• Off-site calling requires one (1) analog phone line (PSTN line)

• Solid LED indicates active call. Flashing LEDs indicate stations that are waiting to be answered. When first call is completed, second call is automatically placed and Command Unit rings. Multiple calls are placed in queue on a “first-in, first-out (FIFO)” basis.

DOWNLOADS

You’ve viewed - of - products